| Features: |
AC input 180 ~ 264 V only Installed on Din rail TS35/7.5 or 15 With
passive PFC function compliance to EN61000-3-2 EN61000-6-2 (EN50082-2)
industrial immunity level Cooling by free convection High Efficiency up to
89% 3 years warranty |
|
| Specifications: TOP |
| Parameter |
Description/SPEC.: |
| AC Input Voltage Range |
180 ~ 264 VAC; 250 ~ 370 VDC |
| AC Inrush Current |
Cold start, 50 A at 230 VAC |
| DC Adjustment Range |
24 ~ 28 V for 24 V model, 48 ~ 53 V for 48 V model |
| Over load Protection |
105% ~ 150% constant current, auto-recovery |
| Over voltage protection |
30 ~ 36V for 24V model, 54 ~ 60 V for 48V model |
| Setup, rise, hold up time |
1200ms, 40ms, 16ms at full load for 230 VAC |
| Withstand Voltage |
I/P-O/P: 3K VAC, I/P-FG: 1.5K VA, 1 minute |
| Working Temperature |
-20 ” ~ 50 ” @ 100%. 70 ” @ 60% load |
| Connection |
I/P: 3 poles, O/P: 4 poles screw Din Terminal |
| EMC Standards |
EN55022 class B, EN61000-3-2,3 |
| |
ENV50204, EN61000-6-2, EN61000-4-2,3,4,5,6,8,11 |
| Weight/packing |
2.4 kgs; 6pcs / 15.0 kgs / 1.75 CUFT |
|
|
| No. |
Model |
Input |
Output |
Iomin |
Iomax |
Load Reg. |
Power |
| 1. |
DRP-480-24 |
250-370 VDC |
+ 24.00VDC |
.00A |
20.00A |
±.00% |
480.000(w) |
| 2. |
DRP-480-48 |
250-370 VDC |
+ 48.00VDC |
.00A |
10.00A |
±.00% |
480.000(w) |
| Other
Informations: TOP |
| DRP-480 |
 |
|
|
|